Visit the Primasonics International web site

Overcurrent protection is optimised for automation

An E-T-A Circuit Breakers product story
Edited by the Engineeringtalk editorial team Feb 20, 2008

Electronic active current limitation responds much faster to overload or short circuit conditions than switch-mode power supplies.

E-T-A Circuit Breakers has developed a new version of its compact ESX10 electronic overcurrent protection product for automation applications.

Designed to reduce costly downtime and danger to personnel on production lines, the new ESX10-T is ready for direct rail mounting, singly or in groups.

Single or group signalling is easily configured.

The type ESX10 electronic circuit breaker provides electronic overcurrent protection according to UL2367 for 24V DC control circuits and load currents from 1 to 12A: in the event of overload or a short circuit, the faulty load will be disconnected electronically by means of a MOSFET in the output circuit of the protector.

It ensures selective disconnection of 24V DC switch-mode power supply (SMPS) loads while optimally matching the application requirements.

The E-T-A ESX10 provides active current limitation to 1.8 or 1.5x its rated current.

This allows capacitive loads up to 20,000uF or lamp loads to be switched on without affecting other loads on the power supply.

At the same time, this electronic active current limitation responds much faster to overload or short circuit conditions than switch-mode power supplies: the ESX10 will shutdown electronically a single faulty output, while allowing all other load circuits connected to the same SMPS to continue working as normal.

The E-T-A ESX10-T is just 12.5mm wide and can be mounted directly on a DIN/EN rail.

All electrical connections are then made by means of convenient screwless terminals.

Status indication is provided by a multicolour LED plus an integral short-circuit-proof status output or potential-free signal contact.

In the event of an overload or short circuit, the load circuit may be re-activated electronically via a reset input, or by a manual on/off button.

The on/off button also allows manual disconnection when starting up a system or during maintenance.

For processes powered by 24V DC switch-mode power supplies without circuits protected by a device such as the ESX10, an overload in a single circuit will cause the power supply to shut down the output to all the circuits it supplies.

On recovery it may go into "hiccup" mode.

Costly downtime, scrap and even danger to personnel may result.

Traditional protection solutions do not provide the answer.

Circuit breakers with fast operating characteristics would be likely to cause nuisance trips during current peaks and switching on of capacitive loads.

On the other hand MCBs are too slow, and neither delayed operation nor high performance circuit breakers will respond adequately in this situation to overcurrents.

The power supply will therefore switch off completely, bringing all connected loads, ie the entire system, to a standstill.

Find out more about this article. Request a brochure, download technical specifications and request samples here.

Not what you're looking for? Search the site.

Back to top Back to top

Contact E-T-A Circuit Breakers

Other E-T-A Circuit Breakers stories

Newsletter sign up

Request your free weekly copy of the Engineeringtalk email newsletter ...

Visit the Primasonics International web site

Browse by category

All suppliers A - Z

A Pro-talk Publication

A Pro-talk publication