Visit the Anixter Components web site
Click on the advert above to visit the company web site

Product category: Plantwide control
News Release from: GE Fanuc Intelligent Platforms UK | Subject: Cimplicity
Edited by the Engineeringtalk Editorial Team on 21 January 2003

Automation for underground power
distribution

The power supply network for the Tbilisi underground has been automated using Cimplicity control and monitoring software and GE Fanuc PLCs.

Financed with assistance from the World Bank, the power supply network for the Tbilisi underground in Georgia (South Caucasus) has been upgraded by local systems integrator, Semper, from a purely manual control system to an automated system using GE Fanuc's control and monitoring software, Cimplicity, and GE Fanuc PLCs This has not only significantly increased productivity, but has also reduced running costs

GE Fanuc has provided vital support and training during the design and installation of the automated systems.

The underground power supply system contains three different types of substation: one providing a direct 825V to the main contact rail; one containing a step-down transformer which powers other infrastructure such as lighting, ventilation and pumps (this supplies 380, 220 and 110V); and one containing a combination of these two.

Originally, personnel at each substation worked around the clock, manually switching units on and off at a telephone request from the dispatcher at a central location.

They would then confirm their action by a return telephone call.

Now, all of these 26 substations are controlled automatically from this central load dispatching centre (LDC).

Distances between substations are typically between 800 and 1900m, while the most remote one is around 20km away.

The automated control system has a two-tier structure.

The LDC is connected to GE Fanuc 90-30 PLCs at each substation on the higher tier.

Each 90-30 at the substations controls its equipment at a lower tier in accordance with commands received on the higher tier, and supplies data back to the LDC.

The control system is based on three PCs in the central command station, the LDC.

Two are used by operators, who oversee the smooth operation of the network, and one PC acts as the main server.

These PCs run Cimplicity.

The main server controls and monitors around 35000 data points on the Scada network.

It generates alarm messages, if data received from the substations move outside set limits, it archives historical data and operator actions, and it monitors system trends.

The operators sit at the two Cimplicity Viewer stations, supporting the dispatch and receipt of data by the server.

They have access to the main database, to adjust settings if needed, and they acknowledge and react to alarms.

They can also display historical data.

Each of the 26 substations can be called up as a separate screen.

Parts of the electrical circuits, or a piece of equipment in the substation, can be clicked on to display more detail along with the relevant current measurements.

The GE Fanuc 90-30 PLCs at the substation have been programmed using GE Fanuc's Versa-Pro software.

They process the data to and from the LDC at the local level.

Remote substations are monitored and controlled by 90-30 PLCs communicating via dedicated telephone lines to two 90-30s on the network in the LDC.

These 90-30s are fitted with modems, which are a standard option, and communicate data using the GE Fanuc protocol SNP-X.

According to Alex Turmanidze, a Semper manager, "When the system was put into operation, the expectations of the system design were realised.

The choice of GE Fanuc software and hardware has brought about greater protection and thus reliability of the electricity supply to the underground network.

With all necessary information about the whole system available to the central dispatcher, it has enabled more flexible control.

The greatly improved efficiency and central control has also led to money saving on a year-on-year basis".

And with the nature of the system design, and compatibility of any future upgrades of software, the control system can easily be extended with new hardware without any reconfiguration of the network. Request a free brochure from GE Fanuc Intelligent Platforms UK ...

GE Fanuc Intelligent Platforms UK: contact details and other news
Email this article to a colleague
Register for the free Engineeringtalk email newsletter
Engineeringtalk Home Page

Search the Pro-Talk network of sites

Visit the Anixter Components web site