Pressure sensors prevent cavitation damage

An IFM Electronic product story
Edited by the Engineeringtalk editorial team May 1, 2008

The PIM sensor continuously monitors a pump to provide an indication of the operating system pressure and offers independent continuous diagnosis of the pump's condition.

IFM Electronic has released pump diagnostic pressure sensors that detect potential pump damage caused by cavitation, trapped air or gas, blockages and deposits.

The PIM series pressure sensor can perform two functions in one compact housing: pump monitoring and pressure detection.

The sensor continuously monitors a pump to provide an indication of the operating system pressure and offers independent continuous diagnosis of the pump's condition.

Operating as a pump diagnostic sensor, the PIM sensor measures the high-frequency pulsation of a properly operating pump and stores it as a reference.

If changes occur in the system, the pulsations will change.

These changes are immediately detected by the sensor.

If a critical pump condition occurs, such as cavitation, the sensor will provide an alarm signal to a controller.

IFM's condition-based pump monitoring sensor increases machine uptime and reduces damage caused by poor pump operating conditions.

In addition to monitoring a pump, any disturbances around the pump such as trapped air in the medium, clogged filters, deposits in pipes or improperly opened valves are also monitored.

The sensor and its teach function are quickly set up using the numeric pushbutton display.

The sensor's display can display the system pressure and the operating state of the pump via a trend display that graphically depicts the operating state of the pump.

The sensor's second output can be configured as a switching output with hysteresis or window function or as a scalable analogue output.

Due to the high overload resistance of the ceramic capacitive measuring cell, the sensor is suitable for switching off the pump in the event of overpressure.

FDT programming software enables the display of the measured values, analogue output, limit values and the parameter setting of the thresholds for diagnosis.

The stainless steel PIM pressure sensor is designed for sanitary applications and uses a variety of sanitary adapters for a secure fitting in washdown, CIP and SIP conditions.

The sensor is 3A-authorised and meets FDA and EHEDG requirements.

Several M12 cable assemblies designed for wash-down conditions are available from IFM.

Find out more about this article. Request a brochure, download technical specifications and request samples here.

Not what you're looking for? Search the site.

Back to top Back to top

Contact IFM Electronic

Tel +44 20 8213 0000

Other IFM Electronic stories

Newsletter sign up

Request your free weekly copy of the Engineeringtalk email newsletter ...

Browse by category

All suppliers A - Z

A Pro-talk Publication

A Pro-talk publication