Schroff slashes A/C system energy use by a third

A Schroff UK product story
Edited by the Engineeringtalk editorial team Oct 28, 2009

Schroff has cut an air conditioning system's energy use by 35 per cent by fitting hot aisle/cold aisle containment, re-routing cable runs within server cabinets and reconfiguring floor tiles.

The reorganisation also provided headroom for the installation of additional servers in the existing cabinets.

It also reduced the temperature gradient within the server cabinets, extending the life of the servers and improving reliability.

The payback time on the cost of the additional hardware installation was measured in months, not years.

The data centre holds 75 server cabinets arranged in three rows in a computer room with an overall volume of 600m3.

The room was cooled by five 32kW air conditioners; during normal operation, four were running at full capacity with one as a redundant back-up.

After the installation of the Schroff hardware, which was retrofitted to the existing cabinets supplied by a third party, three of the air conditioners running at 50 per cent capacity were enough to cope with the thermal load.

Within the cabinets, the installation of 1U blanking panels at the front of the racks, the rerouting of cable runs, the sealing of the base apertures and the installation of ventilated front doors reduced the top-to-bottom temperature gradient from 10C to less than 1C; because the hot and cold air is segregated, the overall temperature within the cabinets also dropped by about 4C, despite the input temperature from the air conditioner units having increased from 17 to 22C.

Further efficiency savings have been achieved by raising the room temperature from 22 to 28C.

The reduced energy usage, direct cost reduction and the associated reduction in CO2 emissions are a significant step towards carbon-neutral operation of the facility.

Find out more about this article. Request a brochure, download technical specifications and request samples here.

Not what you're looking for? Search the site.

Back to top Back to top

Contact Schroff UK

Tel +44 1442 240471

Other Schroff UK stories

  • Schroff dehumidifier protects from condensation
    Schroff has launched a dehumidifier system that is designed to remove moisture from the air within an enclosure to protect electronic and electrical components from condensation.
  • PCB retainers provide 4000N clamping force
    Schroff has brought out a series of PCB retainers that provide a clamping force of more than 4000N, making them ideal for challenging environments, such as those in defence and aerospace systems.
  • Device fastens AdvancedMC modules into subrack
    Schroff, an electronics packaging specialist, has developed a retention device for securely fastening AdvancedMC modules into a MicroTCA subrack.
  • Schroff enhances power distribution of cabinets
    The Datacoms Division of Schroff UK has enhanced the power distribution capabilities of its range of thermally-managed cabinets through a partnership agreement with Raritan.
  • AdvanceMC modules and carriers
    Schroff quickly realised the advantages of AdvancedMC, an important part of the AdvancedTCA platform. Klaus-Michael Thalau, Product Manager at Schroff explains the design and development thinking.
Newsletter sign up

Request your free weekly copy of the Engineeringtalk email newsletter ...

Visit the Rittal web site

Browse by category

All suppliers A - Z

A Pro-talk Publication

A Pro-talk publication