Malfunctioning motors - the
replace/repair dilemma

Request your FREE weekly copy of the Engineeringtalk email newsletter. News about Industrial Motors and more every issue. Click here for details.

Dave Hawley of Deritend Industries provides a basic guide to when it is best to repair, and when is it best to replace faulty electric motors.

The high cost of plant downtime due to the failure of an electric motor means that the decision to repair or replace should be a simple one; especially in view of the competitive price and availability of new motors However, while this may be true for motors of 11kW or less, the situation for larger motors is much less clear cut

In fact, in the higher kilowatt ranges the repair-versus-replace decision is quite complicated, depending on on variables such as rewind cost, severity of the failure, replacement motor purchase price, motor size, the availability of government grants and simple payback criteria.

Even before the relative benefits of repair versus replacement are considered, what must be appreciated by the motor user is that a motor failure should also be viewed as a systematic failure in itself.

In today's highly pressurised environment for manufacturing and processing, the primary focus should not be on how to get a plant up and running quickly after a motor failure, but how to prevent the failure in the first place.

Prevention is always better than cure, and regular condition monitoring surveys are already conducted in many plants to predict when and how a motor might fail.

Not only does this help plant managers allow for repairs to be carried out on a planned basis, but it can also help avoid being forced into taking the quickest and usually most costly option when an impending problem is identified.

As all plant/maintenance engineers are acutely aware, if an unexpected motor failure does occur, the losses in production, delivery problems and lost revenues can soon spiral out of control.

The most effective way to deal with such situations is to have as much information about the plant and various options available before hand, so that the quickest and most economical solution is immediately apparent.

By conducting a survey of all the motors used in a plant, noting their nameplate information, details of the application requirements and how important they are to production, spare units can be purchased, quickest/cheapest suppliers can be noted and all the information needed to ensure a reliable repair is immediately to hand.

Both the condition monitoring and plant survey should give clues to why a unit has failed, or is failing.

Condition monitoring surveys can include electrical, thermal, noise, vibration and oil analysis, which can identify contaminated windings, failing insulation, bearings and lubrication to give engineers vital information as to the efficiency of the unit, as well as the cost and timescale of repairs.

The equipment survey, on the other hand, provides information that allows engineers to assess the suitability of the motor for its application.

For example, a motor may be burning out because of insufficient power rating, or due to changes in the driven load or gearing as more power or torque output is required.

Environmental factors should also be taken into account, such as increased moisture levels or ambient operating temperatures, and the repair history of the motors can be used for working out the life expectancy of the unit after repair.

Bearings are responsible for over half of all motor failures, and it is usually the result of poor maintenance practices such as overloading, using incorrect or excessive amounts of grease for the application, or lack of cleaning.

To keep downtime to a minimum, standard 415V motors should ideally be kept in stock on site, but it is becoming more common for larger companies to have consignment stocks left on site by a contracted supplier to avoid the investment costs involved.

If holding stock is uneconomical to the provider, or motor tasks are more specialised at a site, making an assessment of the potential suppliers with cost comparisons will also save time and money when the need arises.

When repairing a motor, gaining a good idea of what repair services are offered by a company and the respective costs of each level of repair can also be beneficial to avoid unexpected costs, ie the difference between basic reconditioning, re-insulating, stator rewinding, stator repair, major lamination repair, or a new shaft.

It is a general rule that standard motors of 11kW or less should be replaced, as they are generally stock items available at short notice and are uneconomical to repair; however, testing/dismantling to find the cause of failure is recommended.

Depending on the severity of the failure mode, motors of 11kW and above can be worth repairing.

If the unit proves economical to repair, that repair can be completed quickly to take advantage of a shutdown period or returned to site as replacement stock.

In an emergency breakdown situation, though, the opportunity cost of waiting for an analysis nearly always outweighs the money saved through repair.

Standard replacement units in the 11-250kW range are usually available in less than 48 hours, so these can be a viable option.

Exceptions in the 11-250kW range include servomotors used for high precision automation positioning systems, and motors that have been designed for specialist power transmission applications.

EFF1 high efficiency and ATEX explosive atmosphere motors can also prove to be exceptions, as their complex designs make for expensive replacement, but also for more costly repairs.

Additionally, standard motors that only require an electrical or mechanical overhaul can also be quicker and more cost effective to repair than purchasing a replacement.

Standard motors of 250kW and above are more likely to be repaired, due to the longer lead times for these size motors.

The exception to this rule is when failure is catastrophic - for example where bearing mounts, frames, stator cores or shafts need replacing.

But even if this is the case, over the long term it is often worth repairing the unit and keeping it as a backup.

Some companies can repair motors more quickly depending on the urgency of the job and nature of the failure; however, extra costs may be incurred, putting further emphasis on the need to plan ahead.

A survey should take into account previous repairs, enabling engineers to find out if the damage is isolated to the same area and whether the repair was to the correct standard or if the unit is again unsuitable for the application.

If the damage is limited to these areas, and the previous job proved economical, it is usually worth repairing the unit for a second time, but repairing additional damage may result in diminishing returns.

If a motor has failed due to having the wrong specifications for its job (ie more output is required, it is subjected to dust, moisture or explosive gases), an upgrade repair can match the old motor to these changed conditions.

For example; replacing the insulation can allow the motor to operate at higher temperatures.

Moreover, high speed bearings, lubricants and balancing can also improve rev/min performance.

It is also worth noting that during the repair process, the cause of motor failure can be ascertained and that information fed back to the customer helping to prevent a recurrence of the problem.

When considering whether to repair or replace a motor, it is also worth noting that specialist companies such as Deritend can also increase the efficiency of motors during winding replacement etc, allowing the "whole life costs" of larger motors to be significantly reduced.

By logging these data, and by keeping them up to date as cheaper/more efficient replacements come on the market, plant managers can also make sure that the most realistic payback period is always available.

Unless a plant already has an established survey of all the motors and a sound working relationship with both motor suppliers and repairers, choosing the right company to work with can be a demanding task.

Smaller sites may have all the knowledge required in the hands of a few experienced employees, while larger plants may use consignment stocks and a complex repair schedule with all roles applied to a few key suppliers.

The majority of sites fall in between, with engineers always juggling a number of suppliers who offer the best option for one service, but not for others.

For example, an inexpensive motor supplier may not offer the required support in terms of problem solving for applications, manufacturers may offer custom units but not conduct repairs and large suppliers that leave consignment stocks may not repair units.

Deritend repairs or replaces thousands of motors each year, and specialises in all aspects of motor replacement; from condition monitoring to conducting motor usage surveys, supplying motors off the shelf to repairing motors of any type or size to installing/maintaining the units and providing impartial advice in all these areas.